CAUTION
Cable size:
Current Rating
DC 30 A
DC wiring polarity is divided into positive and negative, which is shown in fi gure 5-4. The connec-
tion should be consistent with the indicated polarity marked on the inverter.
Figure 5-7 DC Wiring Illustration
26
CAUTION!
•
The connection number of PV ARRAY, open circuit
voltage and power of String_1 and String _2 must be
coherent.
•
The connection number of PV ARRAY, open circuit
voltage and power of String _3 and String _4 must be
coherent.
•
The maximum power connected to Input1 and Input2
shall not exceed 11 kw separately.
•
The maximum open circuit voltage of PV Array must not
exceed 1000V.
•
The range of Vmpp of Input1 and Input2 shall be 350~800
Vdc.
•
The maximum power connect to inverter must not exceed
25 kW.
•
The device installed between PV array and inverter
must meet the rating of voltage < 1000 Vdc and < Short
current.
Wire size
6mm
2
/ 10 AWG