Figure 5-5 Ac Plug Illustration - Delta SOLIVIA 15 EU G3 TL Manuel D'utilisation Et D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

The female
cable connector
needs to be
wired as shown
below.
NOTE: Rear view
of cable connector
L2
L3
1 : L1
2 : L2
3 : L3
4 : X
: PE

Figure 5-5 AC plug illustration

PE
L1
X
4 (X) is Empty
Inverter
3.
Next tighten the cable gland (2) to the connector housing
(1). Tightening torque for cable sheath diameters bet-
ween 11 and 20 mm: 6 to 8 Nm. Rotate the coupling ring
(3) to mate the connector with the inverter's AC plug.
Rotate the connector housing and cable
gland to remove them from the coupling
ring.
Slide the connector housing and cable
gland onto the cable.
To wire the connector refer to placement
of L1, L2, L3 and PE shown to the left.
Screw termination is provided to fix the
wires to the contacts.
L1
L2
L3
PE
After wiring the mating connector, screw
the connector housing (1) to the coup-
ling ring (3). To do this push the coupling
ring (3) to the connector housing (1) and
tighten 1-2 Nm.
1.
2.
Cable
Cable
23