10. Decommissioning
Decommissioning Procedure
If it is necessary to put the SOLIVIA 15 TL / 20 TL out of operation for return or maintenance,
please follow the instructions below:
WARNING!
After finishing all the procedures, the user can remove the SOLIVIA 15 TL / 20 TL from the moun-
ting bracket.
WARNING! Death and serious injury may occur if the
below instructions are not carefully followed.
To avoid injuries, please follow the below procedures:
1.
Switch off AC circuit breaker to disconnect with electrical
grid.
2.
Switch off the DC Disconnect switch to disconnect with DC
Disconnect switch.
3.
Use the proper voltage meter to confirm that the AC and
DC power connections are void of any current.
4.
Remove the AC wiring immediately to completely discon-
nect with electrical grid.
5.
Remove the DC wiring to disconnect with PV array.
6.
Remove the Communication module RS485 with the com-
puter connection.
57