Troubleshooting - Dri-Eaz LGR i- Serie Guide D'utilisation

Masquer les pouces Voir aussi pour LGR i- Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ER5 √ SENSOR
CONNECTION ON BD
ER6 CONTACT
SERVICE CENTER
ER7 INVALID
MODEL SETTING
ER8 BUTTON STUCK √
ALL BUTTONS
ER9 PUMP BLOCKED √
CHECK PUMP & HOSE

TROUBLESHOOTING

F A U L T
Water drips out
Unit was unplugged before
when moving
purging was complete.
unit
Unit does not
No power to machine.
operate
Unit not switched on.
Blower wheel
Obstructed blower.
not turning
Not enough time to dry.
Unit operating,
Poor air movement in room.
but room not dry
Excessive moist air infiltration.
Unit collects too
Room air is dry.
little water
Room temperature is too low.
If the problem you are experiencing is not listed here, call your local distributor or contact
our Service Department toll-free at 800-932-3030 for further assistance.
07-01674J F410, F411
Check temp/RH sensor connections.
The high voltage board may need replacing. Contact service.
Incorrect DIP switch settings or firmware version for that specific model. Contact
service.
Press each membrane button and check for proper operation. Membrane overlay
may require replacement. Contact service.
Check for obstructions in drain hose. Check the pump.
C A U S E
Purge unit before moving. See "At the End of the Job," p. 5.
Plug in unit; check power at outlet and at base of unit. Switch
unit on.
Remove duct ring and grill.
Remove obstruction.
Replace duct ring and grill.
Allow more time for drying.
Increase air movement with air movers.
Reduce infiltration.
Check humidity with hygrometer.
Increase room temperature.
Check filter and coils; clean as necessary.
S O L U T I O N
9
Dri-Eaz Products, Inc.