Technical Data; Operating Conditions; Pneumatic Data - Siemens SIPART PS2 Notice De Service

Masquer les pouces Voir aussi pour SIPART PS2:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 51

Technical data

All device versions

Operating conditions

Ambient temperature
● Permissible ambient temperature for operation
Degree of protection
2)
Mounting position
Vibration resistance
● Harmonic vibrations (sine) according to DIN EN 60068-2-
6/05.96
● Bump (half-sine) according to DIN EN 60068-2-29/03.95
● Noise (controlled digitally) according to DIN EN 60068-2-
64/08.95
● Recommended range of continuous operation of the entire
control valve
Climate class
● Storage
● Transport
● Operation
2)
At ≤ -10 °C (≤ 14 °F), the display refresh rate of the display is limited. When using Iy module, only T4 is permissible.
1)
Impact energy max. 1 joule for enclosures with inspection window 6DR5**0 and 6DR5**1.
2)
-20 to +80 °C (-4 to +176 °F) for 6DR55..-0G ..., 6DR56..-0G ..., 6DR55..-0D ... and 6DR56..-0D...
3)
See also
Certificates, approvals, explosion protection (Page 40)

Pneumatic data

Auxiliary power (air supply)
● Pressure
Air quality in accordance with ISO 8573-1
● Solid particulate size and density
● Pressure dew point
● Oil content
Unrestricted flow (DIN 1945)
● Inlet air valve (ventilate actuator)
2 bar (29 psi)
4 bar (58 psi)
6 bar (87 psi)
38
1)
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
-30 ... +80 °C (-22 ... +176°F)
IP66 according to EN 60529 / NEMA 4X
Any; in wet environment, pneumatic connections and
outlet opening not upward
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axes
98.1 m/s² (321.84 ft/s²), 27 to 300 Hz, 3 cycles/axes
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
≤ 30 m/s² (98.4 ft/s²) without resonance peak
According to DIN EN 60721-3-4
1K5, but -40 ... +80°C (1K5, but -40 ... +176°F)
2K4, but -40 ... +80°C (2K4, but -40 ... +176°F)
4K3, but -30 to +80 °C (4K3, but -22 to +176 °F)
Compressed air, nitrogen or purified natural gas
1,4 ... 7 bar (20.3 ... 101.5 psi)
Class 2
Class 2 (min. 20 K (36°F) below ambient temperature)
Class 2
4.1 Nm³/h (18.1 USgpm)
7.1 Nm³/h (31.3 USgpm)
9.8 Nm³/h (43.1 USgpm)
3)
SIPART PS2 (6DR5...)
A5E03436620-01, 03/2011

Publicité

Table des Matières
loading

Table des Matières