5. Call the "4 INITA" parameter. To do this, briefly press the
6. Start the initialization process. To do this, press the
following:
The positioner runs through five initialization steps during the automatic initialization process. Displays for the
initialization steps from "RUN 1" to "RUN 5" are shown in the lower line on the digital display. The initialization process
depends on the actuator used, and takes up to 15 minutes.
7. The following display indicates that the automatic initialization is complete:
Aborting the automatic initialization process
1. Press the
button. The digital display shows the following:
The positioner is in the "Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
The software status is displayed.
After releasing the
Manual initialization of linear actuators
See detailed operating instructions for information on manual initialization of linear actuators.
Commissioning part-turn actuators
Preparing part-turn actuators for commissioning
NOTICE
Setting of the adjustment angle
The usual adjustment angle for part-turn actuators is 90°.
● Set the transmission ratio selector in the positioner to 90°.
Condition
The following conditions must be fulfilled before activating the initialization:
1. You have installed the positioner for the part-turn actuators using the suitable mounting kit.
2. You have connected the actuator and the positioner to the pneumatic lines.
32
button, the positioner is in "P manual mode". The positioner is not initialized.
button. The digital display shows the following:
button for at least 5 seconds until the digital display shows the
button for at least 5 seconds.