7.5.7.2
Constructional design for all device versions
How does it work?
● Range of stroke (linear actuator)
● Angle of rotation (part-turn actuator)
Mounting method
● On the linear actuator
● On the part-turn actuator
Material
● Enclosure
Weight, basic device
Torque for plastic cable gland nut
7.5.7.3
Certificates, approvals, explosion protection for all device versions
Electrical data
For connecting to circuits with the
following peak values
Certificates and approvals
CE conformity
Explosion protection
Explosion protection in accordance with
Intrinsic safety "ia"
Intrinsic safety "ic"
Non-sparking "nA"
Permissible ambient temperature
46
3 ... 130 mm (0.12 ... 5.12") (angle of rotation of the
positioner axis 16 to 90°)
30 ... 100°
Using the mounting kit 6DR4004-8V and, if required, an
additional lever arm 6DR4004-8L on the actuators as per
IEC 60534-6-1 (NAMUR) with a fin, columns, or a plane
surface.
Using the mounting kit 6DR4004-8D on the actuators with
fastening plane as per VDI/VDE 3845 and IEC 60534-6-2:
The required mount must be provided on the actuator-
side.
Makrolon® glass-fiber reinforced polycarbonate (PC)
Approximately 0.9 kg (1.98 lb)
2.5 Nm
U
= 5 V
i
I
= 100 mA
i
P
= 160 mW
i
C
= negligibly small
i
L
= negligibly small
i
The applicable directives and standards applied with their revision levels can
be found in the EC declaration of conformity on the Internet.
Ex markings
ATEX
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
Zone 21:
II 2 D Ex ia IIIC 110°C Db
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
Zone 2:
II 3 G Ex nA IIC T6/T4 Gc
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +60 °C (-40 ... +140 °F)
SIPART PS2 (6DR5...)
A5E03436620-04, 02/2014