5.3
Sequence of automatic initialization
See detailed operating instructions for information on sequence of automatic initialization.
5.4
Parameter
Introduction
Parameters 1 to 5 are the same for all versions of positioner. These parameters are used to adjust the positioner to the
actuator. Normally the parameter setup is sufficient to be able to operate the positioner on an actuator.
If you want to get to know the positioner in detail, gradually try out the effects of the remaining parameters by systematic
testing
Note
Factory-set parameter values are printed in bold in the following table.
Overview
Parameter
Function
1.YFCT
Type of position actuator
2.YAGL
Nominal angle of rotation of the feedback message
3.YWAY
Range of stroke (optional setting)
2)
4.INITA
Initialization (automatic)
5.INITM
Initialization (manual)
Set the transmission ratio selector accordingly.
1)
The parameter only appears for "WAY" and for "ncSLL".
2)
When used the value must correspond with the set range of stroke on the actuator.
3)
Carriers must be scaled to the actuator's stroke value,or if this is not scaled they then must be set to the next
largest scaled value.
SIPART PS2 (6DR5...)
A5E03436620-04, 02/2014
Parameter values
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator without sine correction)
ncSt (part-turn actuator with NCS)
-ncSt (part-turn actuator with NCS, inverse
direction of action)
ncSL (linear actuator with NCS)
ncSLL (linear actuator with NCS and lever)
1)
3)
40 | 50 | 60 | 70 | 90 | 110 | 130
33°
90°
OFF
5 | 10 | 15 | 20
(Short lever 33°)
25 | 30 | 35
(Short lever 90°)
(Long lever 90°)
NOINI | no / ###.# | Strt
NOINI | no / ###.# | Strt
Unit
Degrees
mm
25