WARNING
Exceeded maximum ambient or process media temperature
Danger of explosion in hazardous areas.
Device damage.
● Make sure that the maximum permissible ambient and process media temperatures of the device are not exceeded.
Refer to the information in Chapter "Technical data (Page 34)".
CAUTION
Unsuitable compressed air
Device damage. As a general rule, the positioner must only be operated with dry and clean compressed air.
● Use the customary water separators and filters. An additional dryer is required in extreme cases.
● Use dryers, especially if you operate the positioner at low ambient temperatures.
WARNING
Mechanical impact energy
Protect the 6DR5...0-.G...-.... version of the positioner from mechanical impact energy greater than 1 joule; this ensures
adherence to the IP66 degree of protection.
NOTICE
Impact energy and torque
For versions 6DR5a.b-.Gc..-...., where a = 0, 2, 5, 6; b = 0, 1; c = G, N, M, P, Q, the following is applicable:
The device must be protected against power surges of over one joule.
For versions 6DR5a.b-.Gc..-...., where a = 0, 2, 5, 6; b = 0; c = G, N, M, P, Q, the following is applicable:
The maximum torque on the thread of the cable gland should not exceed 67 Nm.
3.1.1
Proper mounting
NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper mounting.
● Before installing ensure there is no visible damage to the device.
● Make sure that process connectors are clean, and suitable gaskets and glands are used.
● Mount the device using suitable tools. Refer to the information in Chapter "Constructional design (Page 35)", for
example installation torques requirements.
CAUTION
Loss of degree of protection
Damage to device if the enclosure is open or not properly closed. The degree of protection specified on the nameplate or in
Chapter "Technical data (Page 34)" is no longer guaranteed.
● Make sure that the device is securely closed.
3.2
Mounting the linear actuator
For linear actuators, use the "linear actuator" mounting kit 6DR4004-8V or the integrated attachment.
You require different installation parts depending on the selected actuator type. The mounting kit is suitable for a stroke of 3
to 35 mm. For a larger stroke range, you require a separately ordered lever 6DR4004-8L. Refer to the detailed operating
instructions for further information on mounting.