Siemens 6DR5 Serie Mode D'emploi page 13

Masquer les pouces Voir aussi pour 6DR5 Serie:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 51
Requirements
● The positioner is mounted.
● You know whether the transmission ratio is to be set to 33° or 90°.
● The positioner has been commissioned successfully, i.e. initialization was completed with "FINISH".
Procedure
NOTICE
The following is applicable for the "flameproof enclosure" version:
● A friction clutch is provided on the outside of the positioner axis. Change the work area using this friction clutch.
● Do not open the flameproof enclosure of the positioner in explosion-prone atmospheres.
Fix the setting acquired by initialization as follows:
1. Make sure the gear latch
2. Make sure the transmission ratio selector
3. Fix the transmission ratio with the gear latch
until the gear latch
to 90°
. The transmission ratio is locked.
Note
Changing the setting of the transmission ratio selector
The setting of the transmission ratio selector
position
.
4. To fix the friction clutch
5. Use the screwdriver to turn the friction clutch gear latch
locked.
3.6
External position detection
WARNING
External position detection system
Versions with flameproof enclosures may not be operated with an external position detection system.
The aforementioned measures are not adequate in some applications. For example, continuous and strong vibrations, high
or too low ambient temperatures and nuclear radiation.
The position detection system and the control unit are mounted separately for these applications. A universal component is
available for this purpose. It is suitable for part-turn and linear actuators. You will require the following:
● An external position detection system with the order number C73451-A430-D78 comprising a positioner enclosure with
an integrated friction clutch, potentiometer as well as different blanking plugs and seals.
● Or a contactless explosion-proof non contacting system (e.g.6DR4004-6N).
● A positioner
● A three-pole cable to connect components.
● An EMC filter module with the order number C73451-A430–D23 is provided in a set along with cable clamps and M20
cable glands.
The EMC filter module is always used for the control unit whenever an external position detection system is used instead of
the internal position sensor. An external position detection system is, for example, a potentiometer with a 10 kΩ resistance
or a non contacting system.
SIPART PS2 (6DR5...)
A5E03436620-04, 02/2014
is in neutral position
is in the correct position.
locks. Turning right locks the transmission ratio to 33°
insert a standard approx. 4 mm wide screwdriver in the friction clutch gear latch
. The neutral position is between 33° and 90°.
. Turn the gear latch
with a standard approx. 4 mm wide screwdriver
can only be changed effectively if the gear latch
counterclockwise until it engages. The friction clutch
. Turning left locks the transmission ratio
is in the neutral
.
is
11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sipart ps2

Table des Matières