APPENDIX A: TROUBLE SHOOTING & SUPPORT
If the UPS is not functioning properly, you can refer first to this chapter for simple
troubleshooting before contacting your reseller. This could save you time and effort
but if the problem persist, then consult your service provider.

A.1.1 UPS

The LED and the acoustic signals are a profit tool to individualize immediately possible
problems
Situation
Mains normal but LED is
off.
Alarm
buzzer
continuously
Utility is normal.
No LED display on the
front panel
UPS does not provide
expected backup time.
The
UPS
normally, but the site
wiring fault indicator is
lit.

A.1.2 Battery and ICS

Situation
Backup time
1. Is the power switch on?
2. Check the ICS?
3. Is the power cord loose?
beeps
1. Check the load status
when
1. The UPS's battery is weak
due to recent outage.
2. The UPS's battery is near
the end of its service life.
operates
1. Building wiring error such
as missing ground or hot to
neutral wire reversal.
The battery backup time (sometime called battery reserve time
or battery autonomy) is the length of time the battery will
supply power to the load during a power failure. You can check
on the Appendix Backup Time.
Check Items
Solution
24
Solution
1. Press Main Switch on.
2. Push the ICS button.
3. Re-connect the power
cord properly.
1. Remove some uncritical
load.
1. Contact Atlantis.
1. Charge the battery.
2. If the battery is near
the end of its service
life, you have to replace
the battery.
1. Call
a
electrician in order to
correct
the
wiring.
ENG
qualified
building