When the unit is operating in this mode, there is a 50% power de-rating. This means that only 50% of the
UPS nominal power can be used when operating in this mode.
UK
If the unit is operating as a Frequency Converter, neither can ECO Mode be activated nor can the unit be
forced to Bypass Mode.
For details on how to enable/disable this mode, please refer to 4.4.6.

4.1.6 Other Operating Details

This section covers other functionalities featured by the unit. For operating details on them, please see
sections 4.2, 4.3 and 4.4.
a) Green Power Function: when the unit is on battery mode and there is no output load, the unit
automatically shuts down after fi ve minutes for battery and energy saving.
b) Cold Start: when this functionality is enabled, the unit has the capability to start up when mains power is
not present, thus powering the load directly from the batteries.
ATTENTION: When the UPS is started for the fi rst time, AC power must be present
c) Auto-Restart: when this functionality is enabled, the unit automatically starts up after autonomy time has
fi nished upon mains power comeback. Otherwise, it is necessary to start up the unit manually.
NOTE: assuming that this functionality is activated, if there is a mains failure just after the unit has
automatically started up, autonomy time will be short as the batteries have not been fully charged.
d) Site Wiring Fault detection: the unit can detect if input line and input neutral have been inverted and
report a fault in that case.
e) Battery test: the UPS can perform a battery test in two different ways: manually, upon user request, or
automatically, with a fi xed interval between tests.
f) Controllable outlets: this UPS includes two groups of output controllable sockets (outlet 1 and outlet 2).
Each group can be confi gured to automatically shut down when the remaining battery capacity goes below
a certain value (75%, 50%, 25% or 0%) or upon user request.
ATTENTION: It is suggested that the highest priority equipment be attached to the main outlets and that
lower priority loads be attached to the controllable outlets.
g) Remote On Off (ROO) / Remote Power Off (RPO): the unit has terminals on the rear side that allow the
user to remotely shut down and start up the unit (ROO) or remotely shut down the unit without the option of
re-starting it remotely (RPO). For operating details, please see section 4.4.8.
h) Compatibility with gensets: this UPS can operate with most of the gensets available in the market.
4.1.7 Block Diagram
17