Rack/Tower Units (Battery Packs); Storage; Temperature Limits; Handling - Chloride Power Protection ACTIVE Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 120
Chloride Active
UK
1000, 1500 and 2000VA models
3000VA models
1 x connection cable Schuko
(male) - IEC320 C19 (female) for
2 x connection cables IEC320
the UPS input
C14 (male) - IEC C13 (female)
1 x multisocket extension
for the UPS output
IEC320 C20 (male) - 3 x Schuko
(female) for the UPS output
- 1 x RS232 interface cable
- 1 x USB cable
- 2 x front brackets for rack-mounting and required mounting hardware
- 2 x sets of tower feet for fl oor-mounting
- 2 x sliding rail kits for rack-mounting (optionally) and required mounting hardware

3.3.4 Rack/Tower units (battery packs)

- 1 x Battery Pack unit
- 1 x battery extension cable
- 1 x battery pack detection cable for auto-detection of number of battery packs connected
- 2 x front brackets for rack-mounting and required mounting hardware
- 2 x spacers to be assembled with the sets of tower feet for fl oor-mounting
- 1 x plate for securing the battery pack to the UPS for fl oor-mounting
- 2 x sliding rail kits for rack-mounting (optionally) and required mounting hardware

3.4 Storage

If it is not intended that the UPS be used within seven days of delivery, attention shall be paid to the storage
conditions.
The UPS should be stored in a clean, dry environment and away from temperature extremes. It is
recommended that the unit be stored in a temperature controlled, moderate humidity environment. The
table below provides the temperature and humidity storage limits:
-25ºC/50ºC (w/o batteries)

Temperature limits

-15ºC/40ºC (with batteries)
Relative humidity (non-
10-90%
condensing)

3.5 Handling

The UPS must be kept upright at all times and handled with care. Damage may be caused if dropped or
subjected to severe impact.

3.6 Environmental Conditions

The UPS tower version must be installed vertically. The UPS rack/tower version (RT hereinafter) can be
installed vertically or horizontally, depending on the desired arrangement.
In any case, it must be installed on a level and even surface and in an area protected from extremes of
temperature, water, humidity and the presence of conductive powder or dust (see section 3.10). Do not
stack units and do not place any objects on top of a unit.
The functional temperature range of the UPS is specifi ed in section 8 ("Technical Specifi cations").
The ideal ambient temperature range is 15ºC to 25ºC.
Expected battery runtimes and battery life is defi ned at 20ºC. Increments of temperature above 25ºC will
reduce the expected battery life.
12
945044.066