7 - CONTROL
Circuit 2
Address id
Description
4630
Remote controls
4631
Remote supply heat
H2O setpoint
4632
Remote supply cool
H2O setpoint
Remote air temperatu-
4633
re
4634
Remote R.H.
4635
Remote dew tempera-
ture
4636
Flat register
U:M:
Bitmap
Bit
Function
0
1=ON / 0=OFF
1-6
Free
7
Remote request
8-15
Free
°C*10
Setpoint
°C*10
Setpoint
°C*10
Temperature probe
%
Humidity probe
°C*10
Temperature probe
Bitmap
Bit
Function
0
EnSetAcquaRete
1
EnSondaAriaRete
2
EnSondaUmiditàRete
3
EnStatoRete
4
EnTempRugiada
5
EnChiamataRete
Free
6-15
Enable
EnStatoRete=1
0 = OFF
1 = ON
EnChiamataRete=1
0 = Request from digital input
1 = Request from network
EnSetAcquaRete=1
EnSetAcquaRete=1
EnSondaAriaRete=1
EnSondaUmiditàRete=1
EnTempRugiada=1
Enable
0: Local
Enables the network set point,if the
1: Network
latter fails it maintainsthe last value
coming from thenetwork
0: Local
0: the ambient thermostatreading
1: Network
applies (H1)
1: the networked value applies;if the
latter fails, the thermostatreading
applies
0: Local
0: the thermostat reading applies
1: Network
1: the networked value applies;
if the latter fails, the thermostat
reading applies
0: Local
Enables on-off of the circuit
1: network not forceable
from remote
0: Local
0: the calculation made by the
1: Network
board applies
1: the networked value applies;
if the latter fails, the calculation
made by the board applies
0: Local
0: request from digital inputs
1: request from bit7 of the
1: Network
remote control