Airwell PAC BTE UI 4 Manuel D'utilisation page 63

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7 - CONTROL
Circuit 2
Address
Id
Description
1
Current H2O set point
4530
4531
2
Return H2O operating temperature
4532
3
Supply H2O operating temperature
4
Averaged temperature variation
4533
4534
5
Instantaneous temperature variation
4535
64
Statuses and alarms bitmap
7
Circulator
4536
4537
8
Valve position (calculated)
4538
9
PID output calculation
10
Valve request correction
4539
4540
11
Correction scan timer
4541
12
Valve relay activation duration
13
Dew operating temperature
4542
4543
14
Air operating temperature
4544
15
Operating R.H.
U:M:
°C*10
Setpoint
°C*10
Temperature probe
°C*10
Temperature probe
°C*10
Temperature Delta
°C*10
Temperature Delta
Bitmap
Bit
Function
Circulator
0
1
Anti-lock
2
Valve in full recirculation (or full
open) position
In posizionamento tutto ricircolo (o in
3
tutto aperto)
Anti-ice
4
5
Circulator pump forcing due to
compressor start-up
6
Set point limited by dew point
7
Call
8
Supply temperature beyond limits
9
Circulator pump thermal alarm
10
Defective return probe
11
Defective supply probe
12
Antifreeze alarm
Secondary on/of
13
14
Free
15
Free
%*10 (0...1000)
Circulator
%*10 (0...1000)
-1000...1000
%*10 (-100...100)
Sec
Sec
°C*10
°C*10
%
Notes
Configuration
1=On
1=Function running
1=Positioned
1=In positioning
1=under way
1=under way
1=active
1=In energy request mode
1=active
1 =on / 0=off
63