Airwell PAC BTE UI 4 Manuel D'utilisation page 21

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4 - REFRIGERATING CONNECTIONS
4.3 - INTERNAL UNIT VACUUM OPERATION
is delivered with charged refrigerator circuits in the following
manner:
Internal unit
External unit charged with refrigerant (voltage 220-240/1/50)
Size
4kW
2,5
R410a
kg
* total char-
5,22
t CO2-eq
ge
External unit charged with refrigerant (voltage 220-240/1/50)
Size
12kW
R410a
kg
3,9
* total char-
8,14
t CO2-eq
ge
* It contains fluorinated greenhouse gases
External unit charged with refrigerant (voltage 380-415/3/50)
Size
10kW
4,2
R410a
kg
* total char-
8,77
t CO2-eq
ge
* It contains fluorinated greenhouse gases
The refrigerant charge present in the external unit is sufficient
up to 5 meters of distance between the 2 units.
Lengths of ducting exceeding 5 metres
Further refill for distance
exceeding 5 metres
Nitrogen precharge
6kW
8kW
10kW
2,5
2,8
3,9
5,22
5,85
8,14
14kW
16kW
3,9
3,9
8,14
8,14
12kW
14kW
16kW
4,2
4,2
4,2
8,77
8,77
8,77
0,054 kg / m
A
VAC vacuum gauge cock
B
REF refrigerant cock
C
HIGH high pressure cock
D
liquid high pressure pump
Refrigerant pipe
E
Vacuum pump pipe
F
Low pressure pipe
H
I
LOW low pressure cock
After having completed the refrigerating connections the
sealing of the refrigerating circuit must be checked:
maintain close the indoor unit cocks 1 and 2
connect pipes D and H to cocks 1 and 2
close cocks A, B, C and I
connect E to the nitrogen cylinder
open cocks C and I
perform the tightness test
Mode 1: open cock B, pressurize the circuit up to 45
bar (see
the label) and wait few hours.
Mode 2: open cock B, pressurize the circuit up to 65
bar (as according to UNI-EN 378-2 2009:PS x 1,43 law)
spray using a leak detector spray cocks and pipes and
check if bubbles are present (gas leaks)
if everything is OK, proceed
discharge the nitrogen from the unit
1
Liquid line
2
Gas line
21