7 - CONTROL
Address
Description
FlagRegister 2
2602
2603
RemoteHeatSet
2604
RemoteCoolSet
2605
RemoteDWHSet
2606
RemoteReturnTemperature
2607
RemoteSupplyTemperature
2608
RemoteFreshAirTemperature
2609
RemoteStorageTemperature
2610
RemoteAmbientTemperature
RemoteFlowAuxiliaryTemperat
2611
ure
Free
2612
2613
Free
2614
DemandLimitRem
2615
RemoteAmbientSet
2616
RemoteAmbientRelativeHumidi
ty
2617
RemoteTemperatureDew
U.M.
Bitmap
Bit
Function
0
EnSetAmbienteRete
1
EnRichiestaAmbRete
EnSondaURAmbRete
2
EnACSControlRete
3
4
free
5
EnSoloCaldaiaRete
6
EnTempRugiada
7-15
Free
°C/10
Setpoint
°C/10
Setpoint
°C/10
Setpoint
°C/10
Temperature
°C/10
Temperature
°C/10
Temperature
°C/10
Temperature
°C/10
Temperature
°C/10
Temperature
kW
Limit
°C/10
Setpoint
%
Humidity probe
°C*10
Temperature probe
Note
Enable
Room thermoregulation request via
network
0: room thermostat reading
1: networked sensor reading
To control DHW via the network,
enable 2709_RegistroFlagACS
To control the "Boiler only"
command via the network
Dewpoint sensor enable via
network
EnSetPointRete = 1
EnSetPointRete = 1
EnSetSanitariaRete = 1
EnSondaRipresaRete = 1
EnSondaMandataRete = 1
EnSondaTExtRete = 1
EnSondaAccumuloRete = 1
EnSondaAriaRete =1
EnSondaMandataAuxRete =1
EnDemandLimitRete = 1
EnSetAmbienteRete = 1
EnSondaURAmbRete = 1
EnTempRugiada=1
Note
Remote room setpoint
enable
Remote room
thermoregulation request
enable
Remote external relative
humidity enable
Remote DHW control
enable
Remote boiler only enable
Enable networked dewpoint
register 2617
Heating setpoint set by
supervisor
Cooling setpoint set by
supervisor
DHW setpoint set by
supervisor
System return temperature
controlled by supervisor
System delivery
temperature controlled by
supervisor
External air temperature
controlled by supervisor
System storage tank
temperature controlled by
supervisor
Room temperature
controlled by supervisor
Auxiliary delivery
temperature controlled by
supervisor
Demand limit value
controlled by supervisor
Room setpoint set by
supervisor
Room humidity controlled
by supervisor
Dewpoint sent by
supervisor
56