7 - CONTROL
Password-protected unit parameters (installer use)
40
Config-DI2
Configuration of digital input F-DI2
0 = Input disabled
1 = Remote ON-OFF input
2 = Remote mode change input (H/C)
3 = Remote system call input
4 = Second remote system set point
41
PipeType
Pipe length configuration (refrigerant line)
0 = short pipe (0 m to 25 m)
1 = long pipe (25 m to 50 m)
188
LimI
Current limit
199
TimePTS
Cycle time for discharge temperature limitation
314
CanAddress
Board CAN address
1=Hydronic board (Master – Internal )
2= Refrigeration board (Slave – External
315
Address
ModBus supervision serial address
316
BaudRate
Baud Rate supervision serial
0=4800
1=9600
2=19200
317
Parity
Parity supervision serial
0=NO
1=Odd
2=Even
321
TimeOutRete
Modbus network timeout
396
EnManualVcc
Compressor manual control enabling
0=automatic control
1= manual control
With Poweroff-PowerOn the parameter is back to the default value (0 = automatic control)
410
SanHeatMode
Management for forced DHW production at instllation thermoregulation in heat satisfied
0=No
1=Yes
2=Yes internal storage
412
CompExtH2OS
Comp. Enabling for External Temp. of sanitary water setpoint
413
MaxCompH2OS
Maximum correction value external T for sanitary water setpoint
420
EnSolare
0=not enable,
1=enable,
432
BandaAcc
Maximum variation allowed inside accumulation during accumulation phase
436
SetAntilegio
Anti-legionella set point
440
TempoRicOn
Pump On time during recirculation cycle
441
TempoRicOff
Pump Off time during recirculation cycle
442
StartRic
Recirculation start time
443
StopRic
Recirculation end time
445
CextMaxS
External temperature maximum ACS compensation in summer mode
446
CextMinS
External temperature minimum ACS compensation in summer mode
455
DeltaTForceR
Delta for resistance activation
456
PWHeaterACS
DHW heater electric power
560
SogliaExtC
Threshold of external temperature under which the boiler is activated
561
IsteresiExt
External temperature hysteresis for HP reactivation
562
TBypassAlm
Alarm transition time from HP to boiler
571
EnSwitchPDC
Enabling of switch between heat pump and boiler in relation to COP
645
PWRes
Integration resi stance absorbed capacity
670
TLimiteCool
Inlet water temp under which comp activation in COOL is permitted
671
TLimiteHeat
Inlet water temp under which comp activation in HEAT is permitted
Tab.2