COMMISSIONING
11.1 TEST RUN PROCEDURE BY REMOTE CONTROL SWITCH (PC-ARFPE EXAMPLE)
1 Turn ON the power supply for all the indoor units.
2 For the models with the auto-address function, wait for 3 minutes
approximately. The addressing is automatically performed. (There
is a case that 5 minutes is required according to the setting
condition.) After that, select using language from "Menu". Refer to
the operation manual for details.
3 Press and hold " " (menu) and " " (return) simultaneously for at
least 3 seconds.
a. The test run menu will be displayed.
b. Select "Test Run" and press "OK". The test run settings will be
displayed.
?
N O T E
When "00" is indicated, the auto-address function may be performing.
Cancel "Test Run" mode and set it again.
4 The total number of the indoor units connected is indicated on
the LCD (liquid crystal display). The case of the twin combination
(one (1) set with two (2) indoor units) is indicated "2 units", and
the triple combination (one (1) set with three (3) indoor units) is
indicated "3 units".
a. If the indicated number is not equal to the actual connected number of indoor unit, the auto-address function is not performed
correctly due to incorrect wiring, the electric noise or etc. Turn OFF the power supply and correct the wiring after checking the
following points; (Do not repeat turning ON and OFF within 10 seconds.)
Power supply for indoor unit is not turned ON or incorrect wiring.
-
Incorrect connectionn of connecting cable between indoor u nits or incorrect connection of controller cable.
-
Incorrect setting of rotary switch and dip switch (the setting is overlapped) on the indoor units PCB.
-
b. Press " " (run/stop) to start the test run.
c. Press "
" and set each item.
5 Press " " (run/stop). Start the test run when indicatin the air flow
volume "HIGH" (default setting) and light the operation lamp. At
this time, 2-hour OFF timmer will be set automatically..
16
PMML0389B rev.1 - 07/2016
Meeting Room
A/C
FLTR
MODE SPEED LOUV.
TEMP
COOL
HIGH
Motion Sensor is activated
LOUV.
ADJ
OK
?
Test run screen
Test Run Menu
Test Run
01
Function Selection
Thermistor Selection
/
Input/Output
03
Function 5
SEL.
ADJ
OK
ENT.
RTN.
Test Run Setting: 2 units
MODE
COOL
SPEED
MED
LOUV.
T-RUN TIME 120MIN
SEL.
ADJ
RUN
RTN.
Test Run Setting: 00 unit
COOL
MODE
MED
SPEED
LOUV.
T-RUN TIME 120MIN
SEL.
ADJ
RUN
RTN.
Test Run Setting: 2 units
COOL
MODE
SPEED
MED
LOUV.
T-RUN TIME 120MIN
SEL.
ADJ
RUN
RTN.
Test Run: 2 units
COOL
MODE
SPEED
HIGH
LOUV.
T-RUN TIME 120MIN
SEL.
ADJ
STOP