Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 83
5. Set process empty level (P006: Empty)
Note:
Setting P006 resets Span, if it has not
previously been set to a different value.
Range 0.0000 to 20.00 m (65.6 ft)
Value
Default 20.00 m (65.6 ft) max. range
Empty can be set to any distance: not
necessarily the bottom of the tank.
6. Set measurement range (P007: Span)
Range 0.0000 to 20.00 m (65.6 ft)
Value
19.56 m (64.1 ft)
Default
(See note on next page.)
Span can be set at any distance above
Empty level.
Notes:
• The default setting for Span is based on Operation (P001) and Empty (P006). Span is set to
Empty minus 110% of Blanking distance
that case, Span is set to Empty distance.
• Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the
transducer face.
7. Minimize false reflections: Set P838
(Auto False-Echo Suppression
Distance)
Range:
0.0000 to 20.00 m (65.6 ft)
Value
*
1.000 m (3.28 ft)
Using P837 and P838 (perform this function at low tank levels)
Notes:
• P837 and P838 should be used together to adjust the TVT (Time Varying Threshold) curve.
• Use this function only if there is at least 2 m (6.5 ft) from the reference point to the
material.
• Set P837 and P838 during start up, if possible.
• If the vessel contains an agitator, the agitator should be running.
1.
Default setting for Blanking is 0.3 m (1 ft) plus shield length.
Page EN-12
SITRANS Probe LR – QUICK START MANUAL
reference
point
Span
P006
P007
Empty
1
, unless Operation is set to distance (P001=3). In
8. Enable False Echo Suppression: set
P837 (Auto False Echo Suppression.
0
Value
1
2
Distance
(100% Level)
Space
Level
(0% Level)
Off
Use "learned" TVT
*
"Learn"
1
7ML19985QP81