Step 2 – calculation of cable length and checking of network structure
The maximum cable length is always determined by the type of cable used. The actual
cable length, which is made up of the length of the main cable and the length of the spur
lines, must not exceed this value. The spur lines are also to be checked (refer to Table 2,
Page 15). The following restrictions apply to the specification of the cable length and
network structure:
• Where cable type A is used the cable length L
• Checking the spur line lengths (refer to Table 2, Page 15).
Calculation of actual cable length:
+ Σ L
L
=
L
SEG
main.
=
580 m + 35 m
=
615 m
Checking the conditions
Consideration
L
< L
SEG
perm.
L
< 120 m
spurs
If one of the conditions is not met then the network structure must be revised.
Step 3 – current calculation
The number of field devices that can be connected to the H1 segment depends on the
fieldbus power supply selected (supply voltage and supply current) and the current
consumption of the field devices. Thus, the number of devices that can be connected
is reduced if a field device consumes a basic current of more than 10 mA, e.g. 20 mA.
By adding up the basic currents I
event of a fault I
for the FDE (Fault Disconnect Electronics) and the current for the
FDE
data modulation I
(+9 mA) you can determine the minimum supply current that the
MOD
fieldbus power supply must supply.
If, on switching on the device, the startup I
rent, then the startup current must be taken into consideration in the calculation. The
response current for the FDE (I
ence between the maximum current in the event of a fault and the basic current. The
field device with the greatest response current is taken into consideration in the current
balance sheet.
Provided that no more than one FDE responds, the following condition must be taken
into consideration in the calculation of the segment current I
I
I
Seff.
SEG
where
Σ
I
=
+ max I
SEG
IB
PROline Prosonic Flow 93 FOUNDATION Fieldbus
perm.
spurs
Condition met?
Yes
Yes
of the field devices plus the response current in the
B
current is greater than the basic cur-
startup
) is calculated for each field device from the differ-
FDE
+ I
+ I
FDE
MOD
startup
may be max. 1900 m.
: