6.6

Closing the device

Any foreign matter shall be removed from the apparatus.
In order to ensure the required minimum protection category, the cover
screws are to be tightened down.
Overtightening might impair the protection category.
6.6.1 Closing of enclosure without cover hinges
Align the cover with the base.
Screw in the enclosure screws and tighten them diagonally (test torque
see technical data).
6.6.2 Closing of enclosures with hinged covers
Fig. 10
- Hold the cover tightly with one hand.
- First release the lower and then the upper retension springs with the
other hand.
- Close the enclosure cover.
- Press the enclosure cover onto the base.
- Screw in the enclosure screws and tighten them diagonally.
(Test torque see Technical data)
6.7

Taking into operation

The electrical connection of the device may only be carried out by skilled
staff (IEC/EN 60079-14).
Prior to taking the apparatus into operation, the tests specified in the
relevant national regulations will have to be carried out.
Apart from that, the correct functioning and installation of the apparatus
in accordance with these operating instructions and other applicable
regulations will have to be checked.
Incorrect installation and use of the junction boxes can invalidate
the guarantee.
Fig. 10
3
1
Explosion protected terminal boxes
7
The required maintenance intervals are set according to their
application and should therefore be determined depending on the
conditions of use.
Before opening the enclosure make sure that the apparatus is
disconnected from the voltage, or take the appropriate protective
measures.
In case of intrinsically safe circuits, working is permitted while voltage
applies.
The relevant national regulations which apply to the maintenance/
servicing of electrical apparatus in explosive atmospheres, shall be
observed (IEC/EN 60079-17).
When servicing the apparatus, particularly those parts that are decisive
for the type of protection against explosion, will have to be checked
(e. g.intactness of enclosure, cable glands, efficacy of the cover gaskets).
If during servicing repairs prove to be necessary, section 8 of these
operating instructions will have to be observed.
8
Repairs and overhaul may only be carried out with genuine COOPER
CROUSE-HINDS / CEAG spare parts.
Repairs that affect the explosion protection, may only be carried
out by COOPER CROUSE-HINDS or a qualified electrician (Compe-
tent person) in compliance with the applicable national rules
(IEC/EN 60079-19).
For replacement and repair only original parts from COOPER
CROUSE HINDS-/ CEAG may be used.
Modifications to the apparatus or changes of its design are not permit-
ted, except for the mounting of additional cable entries and the installa-
tion of supply terminals in accordance with the approval of the apparatus.
9
When the apparatus is disposed of, the respective national regulations on
waste disposal will have to be observed.
2
GHG 71

Maintenance/Servicing

Warning against electric shock.
Repairs / Overhaul / Modification

Disposal/Recycling