- V0..V15: Voltage error
If the electronic board has a fault that takes one of its internal voltages to unacceptable levels, the alarm is activated for panel internal voltage
error V0..V15. This error cannot be reset. The code Vx indicates the part of the circuit where the malfunction was found. If this error appears,
check the supply voltages and the wiring. If everything is in order, the E.Box has suffered internal damage and must be repaired.

- OM: Changed operating mode

This message is only a warning and is not an error. It appears only in the alarm log and indicates that the configuration of the E.Box has been
changed, for example from drainage to pressure boosting.
- E0..E15: Internal error
Panel internal error. This error cannot be reset. If this error appears, check the supply voltages and the wiring. If everything is in order, the E.Box
has suffered internal damage and must be repaired.
11

RESET AND FACTORY SETTINGS

11.1

General system reset

To reset the E.Box, switch the panel off and on again. The operation does not delete the settings saved by the user.
11.2

Restoring the factory settings

To restore the factory values, switch off the E.box, wait until the display has switched off completely, press and hold down the "SET" and "+" keys
and turn on the power; release the two keys only when the letters "EE" appear.
After this procedure the configuration wizard starts.
If the display is not present, it is sufficient to change the DIP SWITCH configuration to E.Box not supplied and supply the E.Box again.