Electrical Installation - Festo SRBP-M-CA1- Série Notice D'utilisation

Boîtier capteur
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 13
Removing the indicator ring
1. Turn the indicator ring until the bottom edge of the indicator ring and the bottom
edge of the plastic cap are flush.
2. Pivot the indicator ring around 90° (see Fig. 7).
3. You can now remove the indicator ring from the cover of the sensor box.
1
2
Fig. 7: Removing the indicator ring
Assembling the sections
Caution
If handled improperly, the clips on the position indicator sections could break
off.
• Take care to clip the sections together without breaking off the fastening
clips.
1. Clip the sections of the visual position indicator together in such a way that the
open paths of the valve are displayed.
Fig. 8: Clipping the sections of the indicator ring together
Be sure to make the centre piece (position pointer) and the indicator ring each
from sections of the same colour. One section is included separately.
Fig. 9: Construction of the position indicator – examples
Mounting the position indicator
1. Insert the indicator ring back into the sensor box cover, by reversing the steps
for removal (
also Fig. 7).
2. Push the centre piece (position pointer) of the position indicator back onto the
shaft of the sensor box. Make sure the alignment is correct.
Before you put the cover of the sensor box back in place, you must carry out elec-
trical installation and commissioning (
cover of the sensor box back in place – torque max. 5 Nm.

7.3 Electrical installation

Warning
Use only power units which guarantee reliable electrical isolation of the opera-
ting voltage as per IEC/DIN EN 60204-1. Observe also the general requirements
for PELV power circuits as per IEC/DIN EN 60204-1.
Caution
Installation errors can damage the electronics or cause faults.
– Use an electrical connecting cable with a nominal outside diameter of
5 to 13 mm.
– Make sure that the length of the signal cable does not exceed the permissible
length of 30 m.
– Connect the earth connection (
with large cross-sectional area) to the earth potential.
3
section 7.3). After that you can put the
Fig. 1 aA ) with low impedance (short cable
Caution
The sensor box contains electrostatically sensitive devices. The internal elec-
tronic components may be damaged if they are not handled correctly.
• Observe the handling specifications for electrostatically sensitive devices.
• Discharge yourself electrostatically before fitting or removing components in
order to protect the components against discharges of static electricity.
The electrical connection terminals are built into the device. For electrical in-
stallation you must open the device and remove the terminal strip. To remove it,
see the steps in section 7.1.
1. If not already done, open the cover and release the terminal strip, as described
in section 7.1.
2. Route the electric cable through the cable connector.
3. Use wire end sleeves suitable for the connection and wire the terminal strip
according to the pin allocation – cable cross section max. 2.5 mm²; torque
max. 0.6 Nm.
1)
Circuit diagrams
N/O contact; circuit diagram shows type
1)
SRBP–...–...–...–MSA–1U–
Changeover switch; circuit diagram shows type
1)
SRBP–...–...–...–MWA–1U–
1) The circuit diagrams apply to versions of the product with mid-position sensing.
mid-position sensing, the contacts marked with the footnote 2 in Fig. 11 are not connected (n. c.).
Fig. 10
The pin allocation of the terminal strip varies depending on the SRBP used.
Pin
...-MS-1U
...-MS-20N
...-MSA-1U
...-MSA-20N
1)
1
Plus (+)
Plus (+)
1)
2
Minus (–)
n.c. (not connected)
3
NO_END2
NO_END2
4
NO_END1
NO_END1
2)
5
NO_MID
NO_MID
3) 4)
6
MV_IN (+)
n.c. (not connected)
3) 4)
7
MV_IN (–)
n.c. (not connected)
3) 5)
8
MV_OUT (–)
n.c. (not connected)
3) 5)
9
MV_OUT (+)
n.c. (not connected)
NO = normally open; NC = normally closed; END = end position;
MID = mid-position
1) For the permissible operating voltage range, see section 13, Technical data
2) Only with variants with mid-position sensing SRBP-...-...-A-...; other variants: n. c.
3) Can only be used with variants with valve connection SRBP-...-...-...-2..
4) For optional use to relay the control signal for the solenoid valve – infeed
5) For optional use to relay the control signal for the solenoid valve – forward relay
Fig. 11
4. Connect the earth connection (
with large cross-sectional area) to the earth potential.
5. Carefully plug the terminal strip onto the pin strip. Make sure that release levers
engage properly.
6. Tighten the union nut on the cable connector – torque 2,7 Nm. This ensures the
right tensile load capacity and IP protection class.
N/O contact; circuit diagram shows type
1)
SRBP–...–...–...–MSA–20N–
On versions without
...-MW-1U
Connection
...-MWA-1U
1)
1)
Plus (+)
1)
Minus (–)
NO_END2
NO_END1
2)
2)
NO_MID
NC_END2
NC_END1
2)
NC_MID
n.c. (not connected)
Fig. 1 aA ) with low impedance (short cable
9
1

Publicité

Table des Matières
loading

Table des Matières