Fault
Unit fails to cool, fan in an
internal airflow circuit is not
running.
Unit fails to cool, fan in
internal airflow circuit running.
Unit fails to cool, fans in both
"internal" and "external"
airflow circuits running.
Unit fails to cool sufficiently.
Unit only cools irregularly.
Condensate accumulates in
switch cabinet.
Condensate fails to drain.
22
... in spite of your care and attention a fault occurs?
First of all, check the points listed in the following table. If the fault persists, please call in
an expert.
Remedy
Check primary fuses and connec-
tion to mains.
Check thermostat setting.
Compressor starts automatically
(find cause, limiting values for
usage may be exceeded; call
expert).
Clean condenser. Ensure that
condenser is properly vented.
Check ambient temperature and
internal load.
Call expert, check unit for tightness.
Clean condenser.
Call expert; replace fan.
Check assemblies and air circula-
tion inside switch cabinet. Air intake
and exhaust into/from cooling unit
into switch cabinet must be
unimpeded.
Check thermostat and cable
connections.
Set higher temperature at thermo-
stat.
Close switch cabinet door.
Remedy leakage at switch cabinet.
Clean condensate drainage.
Condensate drainage hose must be
inclined downward without showing
a bend.
Possible cause(s)
No voltage applied to unit.
Unit fails to cool.
Thermostat setting too high.
Motor protection switch of the
compressor or h.p. push button
has responded.
Threshold values for usage
exceeded.
Lack of coolant.
Condenser contaminated.
Fan in internal airflow circuit
faulty. Fan in external airflow
circuit faulty.
Air not circulating properly
inside the switch cabinet.
Thermostat wrongly set or
faulty.
Blow-out temperature too low.
Switch cabinet not sufficiently
sealed.
Condensate drainage clogged.