8.3 Built-in Reservoir (optional, only for side panel cooling unit)

8.4 Power connection

085 408 025b
1) Place the drilling template supplied onto the outer fastening surface of the switch cabi-
net.
2) Drill the holes, and cut out the opening.
3) Place the mounting frame in the cutout and fasten it using the washers and nuts supp-
lied.
4) Fasten the cooling unit in the built-in reservoir, see installation instructions on side
panel cooling unit (see section 8.2).
CAUTION:
The cooling unit must be connected to the mains by means of a disconnecting device
with a contact gap of at least 3 mm when switched off.
No temperature control must be series-connected to the cooling unit feed.
The fuse as indicated on the ID plate must be series-connected as line protection.
Power connection and repairs, if applicable, may only be carried out by authorized
trained electricians.
Both mains voltage and frequency must correspond to the nominal values indicated on
the ID plate of the cooling unit.
Connect the power cables in the switch cabinet.
CAUTION: Excessive voltage will destroy the cooling unit.
This warning refers to cooling units for a nominal voltage of 400 V/440 V
When connecting to a 440 V power supply, the cable for the primary circuit of the control
transformer (T1) must be reconnected from 400 V to 440 V.
Signal cables and switching cables:
Two-core cable
Every cooling unit is provided with a fault signal line (except DTS 7041 and 7061) which
is used for wiring a floating contact that opens whenever certain faults occur (e.g. ex-
cessive pressure in the cooling system, power failure, cable breakage in the fault signal
line). Contact rating = max. 5 A.
Four-core cable with door contact switch (option)
In case of units provided with a door contact switch the fault signal line is additionally
provided.