Code
No.
Name
C0002
Transferring
*
parameter sets
s
with the keypad
uSEr
(Cont.)
C0002
Saving your
*
own basic
s
setting
uSEr
(Continu
ation)
EDK82EV222 DE/EN/FR 13.0
Possible settings
Lenze
Selection
Keypad ð PAR1 (+ FPAR1)
71
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
11
with all other function modules
Keypad ð PAR2 (+ FPAR1)
72
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
12
with all other function modules
Keypad ð PAR3 (+ FPAR1)
73
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
13
with all other function modules
Keypad ð PAR4 (+ FPAR1)
74
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
14
with all other function modules
Controller ð keypad
80
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
20
with all other function modules
Keypad ð function module
40
only with function module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
Function module ð keypad
50
only with function module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
PAR1 ð own basic setting
9
Important codes for quick commissioning
l
Commissioning
IMPORTANT
Overwrite selected parameter set
and, if required FPAR1, with the
corresponding data of the keypad
Copy all available parameter sets
(PAR1 ... PAR4, if required FPAR1) into
the keypad
Only overwrite the module−specific
parameter set FPAR1 with the data of
the keypad
Only copy the module−specific
parameter set FPAR1 into the keypad
For the parameters of the controller
you can save an own basic setting
(e.g. the delivery status of your
machine):
1. Ensure that parameter set 1 is
active
2. Inhibit controller
3. Set C0003 = 3, confirm with v
4. Set C0002 = 9, confirm with v,
the own basic setting is saved
5. Set C0003 = 1, confirm with v
6. Enable the controller
7