Commissioning
Important codes for quick commissioning
Code
No.
Name
C0002
Parameter set
*
management
s
uSEr
Restoring the
delivery status
C0002
Transferring
*
parameter sets
s
with the keypad
uSEr
(Continu
ation)
146
Possible settings
Lenze
Selection
0
0
Ready
Lenze setting ð PAR1
1
Lenze setting ð PAR2
2
Lenze setting ð PAR3
3
Lenze setting ð PAR4
4
Lenze setting ð FPAR1
31
Lenze setting ð PAR1 + FPAR1
61
Lenze setting ð PAR2 + FPAR1
62
Lenze setting ð PAR3 + FPAR1
63
Lenze setting ð PAR4 + FPAR1
64
Keypad ð controller
70
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen
10
with all other function modules
l
IMPORTANT
PAR1 ... PAR4:
l
Parameter sets of the controller
l
PAR1 ... PAR4 also contain the
parameters for the function
modules standard I/O,
application I/O, AS interface,
system bus (CAN)
FPAR1:
l
Module−specific parameter set of
the fieldbus function modules
INTERBUS, PROFIBUS−DP,
LECOM−B, DeviceNet/CANopen
l
FPAR1 is saved in the function
module
Restore the delivery status in the
parameter set selected
Restore the delivery status in the
fieldbus function module
Restore the delivery status in the
selected parameter set of the
controller and in the fieldbus
function module
By means of the keypad you can
transfer the parameter sets to other
controllers.
During the transmission the access to
the parameters via other channels is
inhibited!
Overwrite all available parameter
sets (PAR1 ... PAR4, if required FPAR1)
with the corresponding data of the
keypad
EDK82EV222 DE/EN/FR 13.0