Connection Of Motor / Brake Resistor - Lenze Global Drive 8200 vector Instructions De Montage

Convertisseur de fréquence
Masquer les pouces Voir aussi pour Global Drive 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5
Electrical installation

Connection of motor / brake resistor

Connection of motor / brake resistor
{
Danger!
All control terminals only have basic insulation (single isolating distance) after
ƒ
connecting a PTC thermistor or a thermal contact.
Protection against accidental contact in case of a defective isolating distance is only
ƒ
guaranteed through external measures, e. g. double insulation.
PES
PE
Use low−capacitance motor cables! (Core/core up to 1.5 mm
£ 150 pF/m). Motor cables that are as short as possible have a positive effect on the drive behaviour!
PES
HF shield termination through PE connection via shield clamp or EMC cable gland.
X2.1/PE
Earthing of the 8200 vector at the output
X2.1/BR1, X2.1/BR2
Terminals of brake resistor
X2.2/T1, X2.2/T2
Terminals of motor temperature monitoring with PTC thermistor or thermal contact
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!
Cable cross−sections U, V, W, PE
Type
E82xV251K2C / E82xV371K2C
E82xV551K2C / E82xV751K2C
E82xV152K2C / E82xV222K2C
126
}
T1 T2
X2.2
PE
PES
PE
PES
PE
PE
2
mm
AWG
1
18
1
18
1.5
16
l
8200 vector
W V U
X2.1
BR2 BR1
PES
PES
PES
X2.2
ϑ>
PES
M
3~
PTC
PES
M
3~
£ 75 pF/m; from 2.5 mm
2
Type
E82xV551K4C / E82xV751K4C
E82xV152K4C / E82xV222K4C
X2.1
8200vec009
£ 100 pF/m; core/shield
2
2
mm
1
1.5
EDK82EV222 DE/EN/FR 13.0
AWG
18
16

Publicité

Table des Matières
loading

Table des Matières