5
Electrical installation
Mains connection
Fuses and cable cross−sections according to UL
Fuses and cable cross−sections according to UL
Supply conditions
Range
Description
Fuses
l
Only in accordance with UL 248
l
System short−circuit current up to 5000 A
l
System short−circuit current up to 50000 A
Circuit−breaker
l
Only in accordance with UL 489
l
Manufacturer/type
– ABB: S 200 U Charact. K
– Schneider Electric: Multi9 C60 Charact. C
– Moeller: FAZ−C Charact. C
J Warnings!
Circuit breakers for 400/500 V devices only for use in WYE 480/277V source.
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
Operation with increased rated power
Operation at an increased rated power is not UL−certified.
Operation at rated power
8200 vector
Type
Mains 1/N/PE AC 230/240 V − operation without mains choke/mains filter
E82xV251K2C
E82xV371K2C
E82xV551K2C
E82xV751K2C
E82xV152K2C
E82xV222K2C
124
Rated fuse current / cable cross−section
Fuse
Type
L1, L2, L3, N, PE
[A]
[AWG]
10
10
10
15
20
2 x 16
20
2 x 16
l
: All classes are permissible
rms
: Only classes "CC", "J", "T" or "R" permissible
rms
Type
[A]
16
15
16
15
16
15
14
15
25
30
Circuit−breaker
L1, L2, L3, N, PE
[AWG]
14 4)
14 4)
14 4)
14 4)
2 x 14 4)
2 x 14 4)
EDK82EV222 DE/EN/FR 13.0