Electrical installation
Wiring
EMC−compliant wiring
EMC−compliant wiring
(Design of a CE−typical drive system)
)
Note!
Control cables and mains cables must be separated from the motor cable to avoid
ƒ
interference injections.
Always use shielded control cables.
ƒ
Generally we recommend to shield the cable for the PTC or thermal contact and
ƒ
route it separately from the motor cable.
If you route the cores for the motor connection and the cores for the connection of
ƒ
the PTC or thermal contact within one cable with a common shield:
To reduce interference injections on the PTC cable we recommend to additionally
install the PTC kit type E82ZPEx.
Optimum HF shield connection of the motor cable is obtained by using the terminal
ƒ
2for motor PE and motor shield.