Switch−on sequence
14.
Start the motor parameter identification (C0148)
A
Ensure that the controller is inhibited
B
Set C0148 = 1
C
Enable the controller
If segment c becomes active again after approx. 30 s,
D
inhibit controller again.
15.
Activate the motor temperature monitoring (C0119) if you
have connected a PTC or thermal contact to terminal X2.2
Lenze setting: switched off
When all settings are complete:
16.
Select setpoint
17.
Enable the controller
18.
The drive is now running.
EDK82EV222 DE/EN/FR 13.0
Parameter setting with the XT EMZ9371BC keypad
Comment
Only when the motor is cold!
Terminal X3/28 = LOW
Press TV
l
l
l
l
l
l
Possible settings
E.g. via potentiometer at terminals 7, 8, 9
Terminal X3/28 = HIGH
If the drive does not start, additionally press u
l
Commissioning
Vector control
Terminal X3/28 = HIGH
The identification starts:
– Segment c is off
– The motor consumes current and makes a
high−pitched" tone.
– The motor does not rotate!
Terminal X3/28 = LOW
Identification is completed.
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
Measured and stored:
– Motor stator resistance (C0084) = Total
resistance of motor cable and motor
(¶ 152)