A terminal board is located in the rear part of the operator for the connection of the motor, of any limit switch and for the grounding of the
operator (pic.14-15).
Connect the motor and the grounding as per pic.14-15 and the table.
ARM3000IFC - 230V AC
POS. COLOR
1
Blue
Common
2
Brown
Opening phase (FCA)
3
Brown
Closing phase (FCC)
4
Brown + Blue
Do not connect
5
Black + Blue
Do not connect
T
Yellow / Green
Grounding
Use only control units with electric clutch.
The distance between the control unit and the motor must not exceed 10 – 12 m.
TAU srl recommends its composite cable, Code M-03000CC101;
Place the control unit (external versions) in the immediate vicinity of the motors.
Be careful not to run cables for auxiliary devices inside raceways housing other cables supplying power to large loads or lights
with electronic starters.
In the event control pushbuttons or indicator lights are installed inside homes or offices several metres away from the actual
control unit, it is advisable to decouple the signal by means of a relay in order to avoid induced interference.
7. START-UP
ATTENTION: Cut power before any job on the operator or the controller.
Carefully observe points 10, 11, 12, 13 and 14 of the SAFETY GENERAL RULES.
With reference to the indications in pic. 3 and in the table (see INSTALLATION), set the ducts and carry out the electrical connections of the con-
trol board and of the chosen accessories.
Choose short routes for cables and keep power cables separate from control cables.
1) Power the system and check the status of the LEDs according to the control unit instructions.
2) Program the control board according to the needs by following the given instructions.
8. TESTING THE AUTOMATED SYSTEM
Carefully check operating efficiency of the gate operator and of all accessories connected to it, paying special attention to the safety devices.
Hand the "User Guide" to the end user together with the Maintenance register.
Explain correct operation and use of the gate operator to the end user.
Indicate the potentially dangerous areas of the gate operator to the end user.
9. MANUAL RELEASE
If the gate operator needs to be moved manually due to a power failure or to an actual malfunction, proceed as follows:
1_ Cut power by means of the safety circuit breaker (even in the event of a power failure).
2_ Slide the protective cap, pic. 16;
3_ Insert the key and turn it 90°, pic. 17.
4_ As shown in pic.18, rotate the release lever upward in order to release the actuator.
5_ Open or close the leaf manually.
Note: To keep the gate operator in manual operation the release device must be left in its current position and power must
be disconnected.
10. RESTORING NORMAL OPERATION
To reengage the gate operator, proceed as follows:
1_ Lock the release lever by rotating it downward.
2_ Turn 90° the release key and remove it.
3_ Close the protection cover.
4_ Power up the system and perform some movements in order to check the correct restoring of every function.
11. USE
It is expressly forbidden to use the device for any other purposes or under any other circumstances other than those mentioned. The
electronic control unit (which must feature an electric clutch) allows the following functions to be selected:
automatic : a command impulse opens and closes the gate;
semiautomatic : a command impulse opens or closes the gate.
In the event of a power failure, the gate may be moved manually by activating the "manual release" device. The model ARM3000BI can be pow-
ered by a backup battery and is able to perform at least 15 complete cycles (open and close) with a fully charged battery.
DESCRIPTION
ARM3000BI - 18V DC
POS. COLOR
1
Brown
2
Blue
3
White
4
Blue
5
Red
19
DESCRIPTION
Encoder positive
Encoder negative
Encoder signal
Motor negative
Motor positive