25. Select Superheat setpoint and push
26. With "Arrows up-down" move to 8K and push
27. Select Valve opening at start-up and push
28. With "Arrows up-down" move to 50% and
push
29. With "Arrows up-down" move to page 5 of 11,
select PID integral time and push
30. With "Arrows up-down" move to 100 s and
push
31. With
"Arrows
up-down"
derivative time and push
32. With "Arrows up-down" move to 5.0 s and
push
move
to
PID
15
33. With "Arrows up-down" go to page 6 of 11,
select LowSH protect. threshold and push
34. With "Arrows up-down" select 3K and
35. With "Arrows up-down" move to page 6 of 11
LowSH protect. integral time and push
36. With "Arrows up-down" select 10.0 s and
push
37. With "Arrows up-down" go to page 7 of 11,
select LOP protection threshold and push
38. With "Arrows up-down" move to -38°C and
push
39. With "Arrows up-down" move to LOP
protection integral time and push
40. With "Arrows up-down" move to 5s and push
41. To move to Driver B push and hold for 2
seconds ENTER
and HELP together