25. With "Arrows up-down" go to page 5 of 9,
select LowSH protect. threshold and push
26. With "Arrows up-down" select 3K and
27. With "Arrows up-down" move to LowSH
protect. integral time and push
28. With "Arrows up-down" select 10.0 s and
push
29. With "Arrows up-down" go to page 6 of 9,
select LOP protection threshold and push
With "Arrows up-down" move to -38°C and
push
30. With "Arrows up-down" move to LOP
protection integral time and push
31. With "Arrows up-down" move to 5s and push
32. Push "Esc" to leave the REGULATION
MF 69 TWIN DRIVER CONFIGURATION-SETTING
PROCEDURE
1. Replace the Driver cover with the EVD
Display and provide power to the machine.
2. Display will show the page 1 of 5 with Driver
A as below
3. Push the "Arrow down" to page 2 of 5
4. Select REFRIGERANT and push the Enter
Button
Refrigerant R744.
5. Push again
6. Always at page 2 of 5, check that VALVE is
Carel ExV
12
then the "Arrows up-down" till the
to confirm