Télécharger Imprimer la page

livin flame Skomo Mode D'emploi Et D'installation page 41

Publicité

Les langues disponibles

Les langues disponibles

Connection to the flue pipe
The flue pipe must have internal dimensions not
larger than 20x20 cm, or diameter 20 cm. In the
event of larger dimensions, or of the flue pipe
being in poor condition ( for example cracks, poor
insulation, etc.), it is advisable to fit a stainless
steel pipe of suitable diameter inside the flue pipe
throughout its length, right up to the top. Check
with suitable instruments that there is a draught
between 3 Pa and 10 Pa. This type of connection
ensures the evacuation of the fumes even in the
event of a temporary power cut. At the bottom
of the flue pipe, provide an inspection cap to
allow periodic checking and cleaning, which must
be done annually. Make a gas-tight connection
to the flue pipe, using pipes and connectors as
recommended by us. You must ensure that a
windproof cowl should be fitted which complies
with the standards in force.
Connection to an external flue with insulated
or double-wall pipe
The only type of pipe which is permissible is
insulated (double-walled) stainless steel, smooth
on the inside, fixed to the wall. Flexible stainless
steel pipe must not be used. At the bottom of
the flue pipe, provide an inspection cap to allow
periodic checking and cleaning, which must be
done annually. Make a gas-tight connection to
the flue pipe, using pipes and connectors as
recommended by us. You must ensure that a
windproof cowl should be fitted which complies
with the standards in force. Check with suitable
instruments that there is a draught between 3 Pa
and 10 Pa.
Connection to the flue pipe
For proper functioning, the connecting pipe
between the stove and the chimney or flue duct
must have a slope of not less than 3% in the
horizontal stretches, the length of which must not
exceed 2 metres and the vertical distance between
one tee connector and another (change of direction)
must not be less than 1,5 m. Check with suitable
instruments that there is a draught between 3 Pa
and 10 Pa. At the botton of the flue pipe, provide
an inspection cap to allow periodic checking and
cleaning, which must be done annually. Make a
gas-tight connection to the flue pipe, using pipes
and connectors as recommended by us. You must
ensure that a windproof cowl should be fitted
which complies with the standards in force.
Fig. 2: connection to the
flue pipe.
Fig. 3: connection to
an external flue with
insulated or double-wall
pipe.
7

Publicité

loading