Télécharger Imprimer la page

livin flame Skomo Mode D'emploi Et D'installation page 38

Publicité

Les langues disponibles

Les langues disponibles

Operating area
For proper functioning and a good temperature
distribution, the stove shoul be positioned in a
location where it is able to take in the air necessary
for combustion of the pellet (about 40 m3/h
must be available), as laid down in the standard
governing the installation and in accordance with
local national standards.
The volume of the room must not be less than 30
m3.
The air must come in through permanent openings
made in walls (in proximity to the stove) which give
onto the outside, with a minimum cross-section
area of 100 cm2.
These openings must be made in such a way that
it is not possible for then to be obstructed in any
way. Alternatively, the air can be taken from rooms
adjacent to the one which needs ventilating, as
long as they are provided with an air intake from
the outside, and are not used as bedrooms or
bathrooms, and provided there is no fi re risk such
as there is for example in garages, woodsheds, and
storerooms, with particular reference to what is
laid down in current standards.
It is not permissible to install the
stove in bedrooms, bathrooms, or
in a room where another heating
appliance is installed (fi replace, stove etc.)
which does not have its own independent
air intake. Locating the stove in a room with
an explosive atmosphere is prohibited.
The fl oor of the room where the stove is to
be installed must be strong enough to take
its weight. If walls are fl ammable, maintain
a minimum distance of 20 cm at the rear (A),
of 40 cm at the side (B) and 100 cm at the
front. If the room contains objects which
are believed to be particularly delicate,
such as drapes, sofas and other furniture,
their distance from the stove should be
considerably increased.
In the presence of wood fl oors,
install a fl oor protection surface in
compliance with the rules in force
in the country
4
Connection to the external air intake
It is essential that at least as much air must be able
to fl ow into the room where the stove is installed as
is required for proper combustion in the appliance
and for the ventilation of the room.
This can be effected by means of permanent
openings in the walls of the room to be ventilated,
which give onto the outside, or by single or
collective ventilation ducts.
For this purpose, on the external wall near the
stove, a hole must be made with a minimum free
cross-section of 100 cm2. (equivalent to a round
hole of 12 cm diameter or a square hole 10x10 cm)
protected by a grille on the inside and the outside.
The air intake must also:
• communicate directly with the room where the
stove is installed
• be protected by a grille, metal mesh or suitable
guard, as long as this does not reduce the area
below the minimum • be positioned in such a way
as to be impossible to obstruct.
20 cm (A)
Min.
100
cm
2

Publicité

loading