Electrical installation

Controller mains connection for a mains voltage of 400 V

4.3
Controller mains connection for a mains voltage of 400 V
ƒ Both, the master and the slave must be supplied!
L1
L2
L3
M8
L1, L2,
25-30 Nm
L3
221-264 lb-in
Fig.9-4
Fuses and cable cross-sections for the mains connection
Type
EVF9381-EV
EVF9381-EVV030
EVF9381-EVV060
EVF9381-EVV110
EVF9382-EV
EVF9382-EVV030
EVF9382-EVV060
EVF9382-EVV110
EVF9383-EV
EVF9383-EVV030
EVF9383-EVV060
EVF9383-EVV110
64
Stop!
The user is responsible for sufficient strain relief!
0
BR1
BR2
U
PE
PE
40 mm
M6
PE
15-20 Nm
133-176 lb-in
Mains connection example
BR1, BR2
Brake resistor can only be operated with the variants V060 and V110
For connection see System Manual of 9300 vector
Master terminals
Slave terminals
Master
315A
315A
400 A
1)
Multiple conductor; both conductors must have the same cross-section
2)
Lenze recommends to use fuses of the gRL utilisation category
Observe the national and regional legislation
V
W
L1
L2
L3
M8
L1, L2,
25-30 Nm
L3
221-264 lb-in
Installation to EN 60204-1
2)
Fuse
L1, L2, L3 [mm
Slave
Master
150
315A
1)
2 × 50
150
315A
1)
2 × 50
240
400 A
1)
2 × 95
1
BR1
BR2
U
PE
PE
40 mm
M6
PE
15-20 Nm
133-176 lb-in
2
]
PE [mm
Slave
Master
150
95
1)
2 × 50
150
95
1)
2 × 50
240
150
1)
2 × 95
EDKVF9383 DE/EN/FR 1.0
V
W
9300VEC013
2
]
Slave
95
95
150