NOTE The batteries charge to 80% capacity in approximately 2 hours. However, it is
recommended that the batteries charge for 36 hours after installation or long-term storage.
NOTE If you installed an optional EBM, use the ERM configurator tool on the Software
Suite CD to configure the UPS for the appropriate extended battery runtime.
10. For the AS/400. Set the QUPSDLYTIM system value for the UPS

UPS Monitoring

UPS monitoring is a standard feature of the AS/400 operating system.
QUPSDLYTIM is a timer in the AS/400 that tells the system how long to
run on UPS power before shutting down. Each AS/400 system is initially
assigned a default value for QUPSDLYTIM. A complete description of
QUPSDLYTIM is provided on the AS/400 Information Center Internet
Site at http://publib.boulder.ibm.com/pubs/html/as400/ic2924/info/index.htm.
*NOMAX tells the AS/400 to use customized shutdown software, and if none is available it
will begin shutdown immediately when utility power fails. Do not set QUPSDLYTIM to
"*NOMAX" unless you understand the implications of the "*NOMAX" function as described
at the AS/400 Information Center Internet Site.
®
EATON Powerware
9125 (9910-P10, P11, P15, P16) UPS Installation Guide for IBM
Press the On button.
μ
The
indicator illuminates solid and the bar graph indicators
display the percentage of load being applied to the UPS. The UPS is
now in Normal mode and supplying power to your equipment.
Monitoring feature.
C A U T I O N
®
S
Applications
164201633 Rev A
INSTALLATION
9