Configuration Mode

When the UPS is in Configuration mode, the bar graph indicators
represent the configuration options. Use the control buttons
(On button and
shows the LEDs and Table 16 explains the corresponding options.
NOTE The UPS can be configured while in Battery mode. If the UPS transfers to battery
power while in Configuration mode, the UPS remains in Configuration mode and indicates
Battery mode on the front panel.
1.
2.
3.
NOTE The UPS exits Configuration mode automatically after two minutes.
4.
®
EATON Powerware
button) to modify the UPS configuration. Figure 39
Press the On button and the
beep. The UPS transfers to Configuration mode.
The bar graph indicators flash briefly and then display the enabled
options.
Press the On button to scroll through the options. Each time you
press the button, the UPS beeps. The LED for the selected option
indicates the current setting; flashing represents disabled options
(see Figure 39 and Table 16).
If you press the On button and nothing happens, the UPS is still in
Operation mode. Repeat Step 1 to enter Configuration mode, and
then perform Step 2.
Press the
button ONCE to toggle the selected option on or off.
Repeat Steps 2 and 3 for each option. Scrolling past the last LED
returns to the first configuration option.
Press the On button and the
Configuration mode at any time.
9125 (9910-P30) UPS Installation Guide for IBM
button simultaneously for one
button simultaneously to exit
®
S
Applications
164201636 Rev A
OPERATION
37