Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
EN
Preheating
1)
Suppressor choke
Choke, ITR 701141,
L 5,6 mH, 47-63 Hz,
Irms 3.2A
BU
34
WH
33
YE
32
BU
37
WH
36
YE
35
85499 177 18.06.20
D
C
B
A
Zust.
Lab.Änderungs Index
Diese mit CAD erstellte Zeichnung darf nur per CAD geändert werden !
Compact wall-mounted units – KWL EC 360 W/W ET
5 .3

Wiring diagram

PE
N
L
Device supply line,
2 m 3 x 1,5 mm², 230 V~
PE 1
Mainboard
F1
T4A/250V~
1
1
N
2
N
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
L
11
M1
11
Relay 1
EC
N
extract-/ exhaust air
N
12
13
PE 1
13
L
14
M2
14
EC
N
Relay 2
N
outside-/ supply air
15
PE 1
M1
M2
S.2
letzt.Änd.
Datum
Name
Transfer board
LAN
casing
shielding
8
1
8
1
LED 4
LED 3
YE
GN
Control heating
230V~, max. 2,4 kW
8
1
RJ-45
Delivered:
JP1 jumper plugged
= final resistance 120 Ohm active
Remove when using terminals
43/44/45/46.
Detailed plan:
F-sensor
Nr. 85410-003
extract air
bottom
Attention!!
2
incorrect connection
destroys the elektronik
LED 2
LED 1
GN
RD
PE 1
Heater
Device supply line
Datum
Name
Bez.:
18.06.20
gez.
SS
18.06.20
gep.
Nr.
85499 177
12
RJ-45
RJ-12
PIN
LAN
Analog
1
TX+
+24,5 V / I max 0,9 A
2
TX-
0 - 10 V van level
AnalogDigital
3
RX+
3,9 - 5,9 V Offset
4
TC
LED red
5
RC
LED green
6
1
4
1
6
RX-
GND
7
frei
x
8
GND
x
6
1
4
1
46
BUS-GND
4
45
3
RS485-B
6
1
4
1
RJ-12 RJ-10
44
2
RS485-A
43
BUS +24 V
1
42
Bypass, 0-10 V
41
GND
40
Bypass
39 opens, 40 closes
39
Bypass
38
+ 24V=
8
1 top
37
GND
36
PWM, supply air
35
0-10V, control supply air
4
6
8
34
GND
1
3 5
7
33
PWM, extract air
32
0-10V, control extract air
31
BUS-GND
30
open
BUS +24 V
29
micro
+
-
28
SD
27
26
Clock buffer
battery
25
CR 2032, 3 V
24
23
F2
22
F2A/250V~
KWL EC 360 W
Fig .29
RJ-10
Digital
+24,5 V / I max 0,9 A
BUS A
BUS B
GND
x
x
x
x
not used
BU
CM24
-
1
+ 24V *
BN
+~
2
WH
+~ Y
3
+ 24V *
GN
Control
outside/supply-
WH
air motor
YE
GN
Control
extract/exhaust-
WH
air motor
YE
not used
NTC-sensor
outside air T1
NTC-sensor
supply air T2
NTC-sensor
extract air T3
NTC-sensor
exhaust air T4
HELIOS - Ventilatoren GmbH + Co
Lupfenstr. 8
78056 VS-Schwenningen
Blatt