Circuit Breakers - ABB ACS880-01 Manuel D'installation

Masquer les pouces Voir aussi pour ACS880-01:
Table des Matières

Publicité

10 Update notice
gG fuses DIN 43620 blade style (frames R1 to R9)
Added:
Drive
Min.
type
short-
ACS880-
circuit
1)
01-
current
A
U
= 500 V
N
302A-5
9400
1)
minimum short-circuit current of the installation
Quick guide for selecting between gG and aR fuses
Added and changed:
Drive type
Cable type
ACS880-
01-
Copper
mm
U
= 500 V
N
302A-5
2x(3x95)
U
= 690 V
N
084A-7
3×35

Circuit breakers

Changed:
Drive type
Frame
ACS880-01-
size
U
= 230 V
N
04A6-2
R1
06A6-2
R1
075A-2
R5
087A-2
R5
115A-2
R6
145A-2
R6
gG fuses (one fuse per phase)
Input
current
A
A
A
302
500 2000000 500
Supply transformer minimum apparent power S
Aluminum
Maximum cable length
2
2
mm
10 m
2×(3×120)
572
3×50
ABB miniature circuit
breaker
Type
S 203 M/P-B/C 10
S 203 M/P-B/C 10
S 803 S-B/C 125
S 803 S-B/C 125
-
-
Fuse
2
s
V
Manufacturer
ABB
with gG fuses
50 m
100 m
617
711
141
144
149
1)
kA
5
5
10
(XT2 L 160 Ekip LS/I
10
(XT2 L 160 Ekip LS/I
-
(XT2 L 160 Ekip LS/I
-
(XT4 L 250 Ekip LS/I
Type
OFAF2H500
(kVA)
Maximum cable length
with aR fuses
10 m
100 m
336
372
58
59
ABB moulded case circuit
breaker (Tmax)
Type
-
-
In=160 3p F F)
In=160 3p F F)
In=160 3p F F)
In=250 3p F F)
DIN
size
2
N
200 m
450
61
1)
kA
-
-
65
65
65
65