4 Update notice
Ex motor, sine filter, low noise
Added and changed:
Drive type
ACS880-01-
Nominal use
I
N
A
U
= 500 V
N
302A-5
270
U
= 690 V
N
07A4-7
7.4
09A9-7
9.9
14A3-7
14.3
019A-7
19
023A-7
23
027A-7
27
U
Supply voltage
N
I
Nominal output current (available continuously with no over-loading)
N
P
Typical motor power in no-overload use
N
I
Continuous rms output current allowing 10% overload for 1 minute every 5
Ld
minutes
I
Continuous rms output current allowing 50% overload for 1 minute every 5
Hd
minutes.
* Continuous rms output current allowing 30% overload for 1 minute every 5
minutes.
** Continuous rms output current allowing 25% overload for 1 minute every 5
minutes.
P
Typical motor power in heavy-duty use
Hd
Note 1: The ratings apply at an ambient temperature of 40 °C (104 °F).
Drive type
Output ratings with selection Low noise optimization of parameter
ACS880-01-
U
= 500 V
N
302A-5
U
= 690 V
N
07A4-7
EX motor (ABB Ex motors)
Light-
duty
use
P
I
N
Ld
kW
A
160
257
5.5
7.0
7.5
9.4
11
13.6
15
18
18.5
22
22
26
97.09 Switching freq mode
Nominal use
I
N
A
206
7.0
Output ratings
Heavy-
Nominal use
duty use
I
I
Hd
N
A
A
238
242
5.6
7.0
7.4
9.4
9.9
13.6
14.3
18
19
22
23
26
Light- duty use
I
Ld
A
196
6.7
ABB Sine filter
Light-
Heavy-
duty
duty
use
P
I
N
Ld
kW
A
132
230
4.0
6.7
5.5
8.9
7.5
12.9
11
17
15
21
18.5
25
Heavy-duty use
I
Hd
A
191
5.6
use
I
Hd
A
221
5.6
7.0
9.4
14
18
22