B–34
Liste des données ModBus
Le tableau suivant répertorie les registres de maintien des fonctions de réglage fin du Groupe
"B".
Code
Nom
Fonc.
B001 Selection of automatic
restart mode
B002 Allowable under-
voltage power failure
time
B003 Retry wait time before
motor restart
B004 Instantaneous power
failure / under-voltage
trip alarm enable
B005 Number of restarts on
power failure / under-
voltage trip events
B012 Level of electronic
thermal setting
B212 Level of electronic
thermal setting, 2nd
motor
B013 Electronic thermal
characteristic
B213 Electronic thermal
characteristic, 2nd
motor
Groupe de fonction de réglage fin "B"
R/W
Description
R/W Select inverter restart method,
four option codes:
00... Alarm output after trip,
no automatic restart
01... Restart at 0Hz
02... Resume operation after
frequency matching
03... Resume previous freq.
after freq. matching, then
decelerate to stop and display
trip info.
R/W The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the
restart mode is selected.
R/W Time delay after under-
voltage condition goes away,
before the inverter runs motor
again.
Range is 0.3 to 100 seconds.
R/W Two option codes:
00... Disable
01... Enable
R/W Two option codes:
00... Restart 16 times
01... Always restart
R/W Set a level between 20% and
120% for the rated inverter
current
R/W
R/W Select from two curves,
option codes: *1
00... Reduced torque 1
R/W
01... Constant torque
02... Reduced torque 2
Données du réseau
Registre
Plage
hex
dec.
10A5h 04261 0, 1, 2, 3
10A6h 04262 3 to 250
10A7h 04263
3 to
1000
10A8h 04264
0, 1
10A9h 04265
0, 1
10AD
04269
2000 to
h
12000
1526h 05414
10AEh 04270
0, 1, 2
1527h 05415
Res.
0.1 sec
0.1 sec
0.01%

Publicité