Typical Installation With Generator Below The Waterline; Components; Drainage System - Mase Generators I.S. 21.5 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 19
GENERATORS
4.2.2 Typical installation with generator below the
water line (Fig.5)
1
Sea exhaust
2
Silencer
3
Muffler
4
Water filter
5
Main system tap
6
Sea intake
7
Drain tap
8
Antisiphon valve
9
Drainage
A - Pipes - inner diameter Ø75 mm.
B - Pipes - inner diameter Ø25 mm.
C - Pipes - inner diameter Ø16 mm.
D - Pipes - inner diameter Ø14 mm.
- It is very important to respect the distances shown
in the installation diagrams.
- The mufflers (Ref.3 of Fig.4 and 5 ) have the function
of collecting the water left in the exhaust pipes when
the generator engine is turned off and preventing
that it flows into the engine through the manifold
and the exhaust valve. For this reason it is essential
to respect the position of the muffler and the length
of the pipes as indicated in the installation diagram.
4.3

Components

The sea water intake system must
be separate from the one for the engines propelling
the boat.
1 - Direct sea intake 1/2"
If the unit is installed more than 1
metre above the water-line, a check valve should be
fitted after the sea intake (fig.6, ref.1) to prevent the
water circuit emptying when the motor is off. If this
empties, the rotor of the water pump might be damaged
during start up; for the same reason, when the unit is
first started up, the suction tube from the valve to the
pump should be filled manually.
2 - Ball tap (general) 1/2"
3 - Ball tap (drainage) 1/2"
This is used to drain the cooling system of the
electric generator for general maintenance or when a
long period of inactivity is expected.
4 - Water filter (can be inspected)
This must provide efficient protection for the cooling
circuit from the entrance of mud, sand and seaweed.
Rate of flow IS 21.5-23.5: 40-45 L/min.
GB
The filter mesh should be very fine.
Mesh 2 - 470 micron is recommended, other sizes do
not give good filter performance.
5 - Anti-siphon valve: this is a valve that brings the
cooling circuit back to atmospheric pressure when
the motor is turned off, thus avoiding the formation of
siphons. It's use obligatory when the base of the
generator group is under the water line, and it
must be positioned at least 50 cm. above sea level.
(see fig.5).
Anti-siphon valve must be inserted
between the inlet of the sea water pump and mixing
elbow as indicated in Fig.9.
The drainage duct of the anti-siphon valve must run
beneath the valve itself in order to prevent water
accumulating in the duct, which should always re-
main empty to allow air to pass through when the unit
is switched off. (see fig.7)
It is recommended that the drainage pipe from the anti-
siphon valve be fed into the bilge, as small amounts of
water might be drained through it during normal operation.
The cooling circuit is connected to the heat exchanger
pipe fitting as shown in Figure 8.
4.4

Drainage system

The flue gas/water drainage system of the generator
must be separate from that of the main motors
highest point of the drain duct to the muffler should
not exceed 2 metres. This is to prevent the water left
in the drainage duct returning to the motor after
filling the tank muffler, when the unit is turned off.
1 - Muffler.
This dampens the noise of the drainage and stops the
water flowing back towards the motor. The muffler
should be installed no less than 1 metre away from
the generator and positioned at a height as per
fig.4,5.
2 - Silencer
This further reduces noise. It should be installed no
more than 1 metre from the sea drainage nozzle.
3 - Outboard drainage pipe.
This must be fitted in a position that is constantly
above sea level in all the vessel's possible conditions
of use.
- 16 -
IS 21.5-23.5
The length of the tube from the

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

I.s. 23.5

Table des Matières