Installation space
Reserve space required to install the
indoor unit and for service work.
Ceiling height
<Installable ceiling height list>
Standard (Set-up at factory)
High ceiling
When the ceiling height exceeds 3.5m, the hot air is difficult to reach the floor. In this case, it is necessary to set the
high ceiling or change the discharge direction.
If incorporating a filter sold separately, setup of the high ceiling is also necessary.
For setup of the high ceiling, refer to the items of the Applicable controls "To incorporate a filter sold separately" and
"In case of installation to high ceiling" in this Manual.
The lighting time setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed
according to the condition of installation. If the room is not heated due to the installation place or construction of the
room, the detection temperature of heating can be raised.
For setup method, refer to "Change of lighting time of filter sign" and "To secure better effect of heating" in the
Applicable controls of this Manual.
In case of wireless type
The sensor of indoor unit with wireless remote controller can receive a
signal within approx. 8m. Based upon it, determine a place where the
remote controller is operated and the installation place of the indoor unit.
• To prevent a malfunction, select a place where is not influenced by a
florescent light or direct sunlight.
• Two or more (Up to 6 units) indoor units with wireless remote controller
can be installed in the same room.
3

INSTALLATION OF INDOOR UNIT

Install the air conditioner certainly to sufficiently withstand the weight.
If the strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work to guard against strong wind or earthquake.
An incomplete installation can cause accidents by the units falling and dropping.
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to
use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do not bundle it with PP band at positions other than specified.
250 or more
Installable ceiling height
Up to 3.5m
Up to 4.0m
WARNING
REQUIREMENT
4
250 or more
(Unit: m)
Set-up data
0000
0001