ELECTRIC WORK
Remote controller wiring
• Strip off approx. 14mm cover of the wire to be connected.
• Twist wire of the remote controller to be connected with wire of the remote controller unit (or sensor), and press-fit
them with a wire joint. (Wire joints (White: 2 pieces) are included in the accessory of the main remote controller
(sold separately) or wireless remote controller kit (sold separately).)
• As the remote controller wire has no polarity, there is no problem if connections to indoor unit terminal blocks A
and B are reversed.
<Wiring diagram>
Terminal block
for remote controller
wiring of indoor unit
A
B
Remote controller wire
(Local procure)
Wiring between indoor and outdoor units
Earth leakage breaker
Outdoor power supply
3-phase
380–415V, 50Hz
380V, 60Hz
Central control line wire
Power supply
220–240V
~
220V
60Hz
Remote controller,
for central control, etc.
Earth leakage breaker
Indoor power supply
~
220–240V
50Hz
~
220V
60Hz
Address setup
Set up the addresses according to the Installation Manual attached to the outdoor unit.
Approx. 200mm
W
B
Wire from remote controller unit
Connecting
part
or sensor
Header unit
(Open)
~
50Hz
Switch
W : White
B : Black
Remote
controller unit
or sensor part
Follower unit
(Earth)
Inter-unit wire between outdoor units
Connection of shield
wire closed terminal
Indoor/Outdoor inter-unit wire
Connection of shield
wire closed terminal
Indoor unit
15
Remote controller wiring
Wire from remote
controller or sensor
NOTE
An outdoor unit connected
with indoor/outdoor inter-unit
wire becomes automatically
the header unit.
Earth
Pull box
(Remote controller group operation)
Wire joint
(Earth)