Warning and error codes In case of a warning or error displayed by the inverter, refer to the table
below before contacting technical support if needed.
Code
Type
2
warning_ond
Islanding detected. If this problem remains, please contact your grid operator
Grid voltage higher than the limit of the norm. If this problem remains, please contact your
3
warning_ond
grid operator.
Grid voltage lower than the limit of the norm. If this problem remains, please contact your
4
warning_ond
grid operator.
Grid frequency higher than the limit of the norm. If this problem remains, please contact your
5
warning_ond
grid operator.
Grid frequency lower than the limit of the norm. If this problem remains, please contact your
6
warning_ond
grid operator.
Grid voltage lost. Check if the GRID CONNECTION connector is correctly supplied by the
7
warning_ond
public grid. If this problem remains, please contact your grid operator.
Grid frequency lost. Check if the GRID CONNECTION connector is correctly supplied by the
8
warning_ond
public grid. If this problem remains, please contact your grid operator.
9
warning_ond
There is a phase rotation problem. Reverse 2 phases and restart the inverter.
Grid sinus lost. Check if the GRID CONNECTION connector is correctly supplied by the
10
warning_ond
public grid. If this problem remains, please contact your grid operator.
Average grid voltage greater than norm voltage for 10 min. If this problem remains, please
11
warning_ond
contact your grid operator.
Overload on the AC BACKUP. Remove the high power devices with inrush power (air
12
warning_ond
conditioner, pumps,...).
High inverter temperature. Please check the good ventilation of your inverter and the
13
warning_ond
temperature in the inverter room.
14
warning_ond
Earth default. Please check inverter is correctly connected to the ground.
22
warning_pv
Low PV2 voltage. Check the PV sizing, connection and installation.
PV voltage too high. Check the PV sizing and installation. This problem can cause a critical
23
warning_pv
electronic damage.
PV2 voltage too high. Check the PV sizing and installation. This problem can cause a critical
24
warning_pv
electronic damage.
CPU1 flash failure. Please reboot the inverter and check the version is the last one. If the
25
warning_cpu
problem remains, please contact your distributor.
CPU1 start failure. Please reboot the inverter and check the version is the last one. If the
26
warning_cpu
problem remains, please contact your distributor.
Battery warning reported. Check the battery ID warning in IMEON OS. ONE. If the problem
27
warning_bat
remains contact your battery distributor.
Battery not connected. Please connect the batteries and check if a breaker/fuse is not open
30
warning_bat
between inverter and batteries. If the problem remains contact your battery distributor
Battery voltage too high. Disconnect your battery and check if the battery specifications
32
warning_bat
comply with inverter.
CPU1 communication failure. Please reboot the inverter and check the version is the last
35
error_ond
one. If the problem remains, please contact your distributor.
Internal wiring failure. Please reboot the inverter. If the problem remains contact your
37
error_soft
distributor or IMEON for repair
Software service failure. Please reboot the inverter. If the problem remains, please contact
38
error_soft
your distributor.
Software service failure. Please reboot the inverter. Please reboot the inverter and check the
39
error_soft
version is the last one. If the problem remains, please contact your distributor.
Software service failure. Please reboot the inverter. Please reboot the inverter and check the
40
error_soft
version is the last one. If the problem remains, please contact your distributor.