Safety instructions

This „Annex to operating instructions"
GHG 5107001P0012 is
only for use with the original operating
instructions
"GHG 510 7001 P0001" . The GHG 511 plugs
and sockets are not suitable for Zone 0 and
Zone 20 hazardous areas.
Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in
italics the same as this text!
Explosion-protected plugs and sockets 16 A, GHG 511
1
Technical data
1.1 Plug and socket GHG 511
ATEX type examination certificate:
Marking acc. to 94/9/EC and standard::
EN 60079-0
IECEx type examination certificate:
Category of application:
IEC60079-0
Rated voltage:
GHG 511 -
3-pole
GHG 511 -
4-pole
GHG 511 -
5-pole
Rated current:
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity AC 3, 3-pole:
Switching capacity AC 3, 4-pole:
Switching capacity AC 3, 5-pole:
Perm. ambient temperature:
(catalogue version, special versions permit deviating
temperatures.)
Perm. storage temperature in original packing: -20° C to +40° C
** Protection category acc. to EN/IEC 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to EN/IEC 61140:
Cable entry:
wall socket
Supply terminals:
terminals
Test torques:
Cover screws
Terminals
Weight:
wall socket
4/5-pole
GHG 511 45
Auxiliary contact:
Rated voltage:
Switching capacity:
3
Field of application
The plugs and sockets GHG 511 are suitable
for use in Zone 1, 2 and 21, 22 hazardous
areas acc. to IEC/EN 60079-10-1 and
IEC/EN 60079-10-2!
The enclosure materials employed, including
the exterior metal parts, are made of high-
quality materials which ensure a corrosion
protection and resistance to chemical sub-
stances corresponding to the requirements in
a "normal industrial atmosphere":
- impact resistant polyamide
- glass-fibre reinforced polyester
- special steel AISI 316 L
In case of use in an extremely aggressive
atmosphere, please refer to manufacturer.
PTB 99 ATEX 1039
II 2 G Ex de [ia] IIC T6/T5
II 2 D Ex tD A21 IP66 T80°C
IECEx BVS 12.0027
Ex de IIC T5/T6 Gb
Ex tb IIIC T80°C Db IP66
up to 415 V, 50/60 Hz
up to 690 V, 50/60 Hz
up to 500 V, 50/60 Hz
max. 16 A
max. 25 A
max. 35 A gL
250 V/16 A
400 V/16 A
400 V/16 A
-20° C to +40° C
IP 66 (catalogue version)
II - is complied with by the devices
(catalogue version)
2x blanking plug M25
Cross section
Stripped wire length
2 x 1,5 - 10 mm²
3.0 Nm
4.0 Nm
(catalogue version)
approx. 5.4 kg
250 V AC
AC: 5 A
DC: 0.03 A
4
Use/Properties
The GHG 511 plugs and sockets are used for
the power supply of local controls with varying
locations, as well as of electrical installations,
mobile machinery and driving gear in hazardous
areas.
The plugs and sockets can also be used in a
"normal industrial area" .
The low-voltage plugs and sockets GHG 511
are fitted with a load switch and can be used
up to max. 16 A (see technical data).
The plugs and sockets can generally be used
for the voltage range laid down in
IEC/EN 60309 (e.g. UN 400V that corresponds
to the voltage range 380-415V).
The apparatus connected to the plug shall
be suitable for the applied mains voltage.
GB
16 mm
5