6.4

Closing the device

In order to ensure the required minimum
protection category, the cover screws, the
screws of the plug and of the coupler shall be
tightened down. The screws of the plug and the
coupler shall be tightened down.
Overtightening might impair the protection
category.
Any foreign matter shall be removed from
the device.
6.5

Taking into operation

Prior to taking the apparatus into operation, the
tests specified in the relevant national
regulations shall be carried out. Apart from that,
the correct functioning and installation of the
apparatus in accordance with these operating
instructions and other applicable regulations will
have to be checked.
Check the plug for any damages before
putting it in the socket.
The user must ensure that a uniform equipoten-
tial earth applies throughout when the plug and
socket system is operated.
The inappropriate installation and operation
of the plugs and sockets can entail the loss
of warranty.
10
Explosion protected plug and socket system 16 A,
3-pole, 4-pole, 5-pole, GHG 511
7

Maintenance/Servicing

The relevant national regulations which apply
to the maintenance/servicing of electrical
apparatus in explosive atmospheres, shall be
observed (IEC/EN 60079-17).
Before opening the enclosure, make sure
that the device is disconnected from the
voltage, or take appropriate protective
measures.
The required maintenance intervals depend on
the specific application and will therefore have
to be determined by the user dependent on the
conditions of use.
When servicing the plugs and sockets,
parti cularly those parts that are decisive for
their type of protection against explosion will
have to be checked (e. g. intactness of
flameproof enclosed components, of the
housing, firm fit of the cable entries and
efficacy of gaskets).
If during servicing, repairs prove to be
necessary, section 8 of these operating
instructions will have to be observed.
8
Repair/Overhaul/
Modifications
Repairs and overhaul may only be carried out
with genuine Cooper Crouse-Hinds spare parts.
Should the flameproof enclosure be
damaged, only a replacement will be
permitted. In case of doubt, the respective
apparatus will have to be returned to Cooper
Crouse-Hinds for repair.
Repairs that affect the explosion protection,
may only be carried out by Cooper Crouse-
Hinds or a qualified electrician in compliance
with the applicable national rules
(IEC/EN 60079-19).
Modifications to the device or changes of its
design are not permitted.
9

Disposal/Recycling

When the apparatus is disposed of, the respec-
tive national regulations on waste disposal will
have to be observed.
In order to facilitate the recycling of individual
components, plastic parts are provided with the
identification mark of the plastic material used.
Subject to modifications or supplement of the
product range.